(300/500kVA, 480V)
 
Model
DPH-300K
 
DPH-500K
 
DPH-600K
Power Rating
 
DPH-300K
100,150,200,250,300 kVA
 
100,150,200,250,300 kW
 
Power Module Quantity : Up to 6 units
DPH-500K
300,350,400,450,500 * kVA
 
300,350,400,450,450 kW
 
Power Module Quantity : Up to 9 units
DPH-600K
500,550,600 kVA
 
500,550,600 kW
 
Power Module Quantity : Up to 12 units
Input
 
Nominal Voltage
220/380V, 230/400V, 240/415V (3-phase, 4-wire + G)
Voltage Range
305~478Vac (full load), 228~478Vac (70% load)
Current Harmonic Distortion
< 3% **
Power Factor
> 0.99
Frequency Range
40 ~ 70 Hz
Output
 
Voltage
220/380V, 230/400V, 240/415V (3-phase, 4-wire + G)
Voltage Harmonic Distortion
≤ 0.5% (linear load)
Voltage Regulation
±1% (static)
Frequency
50/60 ± 0.05 Hz
Overload Capability
≤ 125% : 10 minutes
 
≤ 150% : 1 minute
 
> 150%: 1 second
Display
10” color touch screen
Interface
 
Standard
RS232 x 1, Parallel port x 4, USB type A x 2, USB type B x 1, MODBUS x 1, Smart slot x 1, REPO x 1, EPO x 1, Input dry contact x 4, Output dry contact x 6, External battery temperature detection x 4, External switch/breaker status dry contact x 4, BMS (RJ45) x 1, Ethernet x 1
Optional
Relay I/O card, Battery cabinet temperature sensor cable
Conformance
 
Safety
CE
Efficiency
 
AC-AC Mode
Up to 96.5%
ECO Mode
99%
Battery
 
Nominal Voltage
±240 Vdc (default, ±180Vdc to ±276Vdc configurable)
Charge Voltage
±272V (adjustable from 204V to 312V)
Protection of Battery Deep Discharge
Yes
Environment
 
Operating Temperature
0 ~ 40 ℃
Relative Humidity
0 ~ 90% (non-condensing)
Audible Noise (at one meter)
DPH-300K : < 75 dB
 
DPH-500K : < 80 dB
 
DPH-600K : < 85 dB
IP Protection
IP 20
Others
 
Parallel Redundancy and Expansion
Module and system redundancy, Maximum 8 units
Emergency Power Off
Remote (default) and local (optional)
Battery Start
Yes
Physical
 
Dimensions (W x D x H)
DPH-300K : 600 x 1100 x 2000 mm
 
DPH-500K : 600 x 1100 x 2000 mm
 
DPH-600K : 1200 x 1100 x 2000 mm
Weight : UPS System (without power modules)
DPH-300K : 311 kg
 
DPH-500K : 317 kg
 
DPH-600K : 605 kg
Weight : 50kW Power Module (optional)
36 kg
* The power module's power rating is adjustable to either 50kVA or 55.6kVA via touch panel.
** When input vTHD is less than 1%.

All specifications are subject to change without prior notice.

 