Modular UPS - DPH Series, Three Phase, 50- 300/500/600 kW

Technical Specifications

Product available regions :
Because product specifications vary slightly from region to region, please download your local leaflet or visit your local website for detailed product information.
EMEA North America South America SEA India China Taiwan South Korea

(300/500 kVA, 480 V)
 
Model
DPH-300K / DPH-500K / DPH-600K
Power Rating
 
● DPH-300K
50-300 kVA/kW
 
50 kW Power Module: Up to 6 units
● DPH-500K
50-500* kVA / 50-450 kW
 
50 kW Power Module: Up to 9 units
● DPH-600K
50-600 kVA/kW
 
50 kW Power Module: Up to 12 units
Input
 
Nominal Voltage
220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)
Voltage Range
305~478 Vac (full load), 228~478 Vac (70% load)
Current Harmonic Distortion
< 3% **
Power Factor
> 0.99
Frequency Range
40~70 Hz
Output
 
Voltage
220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)
Voltage Harmonic Distortion
≤ 0.5% (linear load)
Voltage Regulation
± 1% (static)
Frequency
50/60 Hz ± 0.05 Hz
Overload Capability
≤ 125%: 10 minutes
 
≤ 150%: 1 minute
 
> 150%: 1 second
Display
10” color touch screen
Interface
 
Standard
RS232 x 1, Parallel port x 4, USB type A x 2, USB type B x 1, MODBUS x 1, Smart slot x 1, REPO x 1, EPO x 1, Input dry contact x 4, Output dry contact x 6, External battery temperature detection x 4, External switch/breaker status dry contact x 4, BMS (RJ45) x 1, Ethernet x 1
Optional
Relay I/O card, Battery cabinet temperature sensor cable
Conformance
 
Safety
CE
Efficiency
 
AC-AC
Up to 96.5%
ECO Mode
99%
Battery
 
Nominal Voltage
± 240 Vdc (default, ± 180 Vdc to ± 276 Vdc configurable)
Charge Voltage
± 272 V (adjustable from ± 204 V to ± 312 V)
Protection of Battery Deep Discharge
Yes
Environment
 
Operating Temperature
0~40°C
Relative Humidity
0~90% (non-condensing)
Audible Noise (at one meter)
 
● DPH-300K
< 75 dB
● DPH-500K
< 80 dB
● DPH-600K
< 85 dB
IP Protection
IP20
Others
 
Parallel Redundancy and Expansion
Module and system redundancy, Maximum 8 units
Emergency Power Off
Remote (default) and local (optional)
Battery Start
Yes
Physical
 
Dimensions (W x D x H)
 
● DPH-300K
600 x 1100 x 2000 mm
● DPH-500K
600 x 1100 x 2000 mm
● DPH-600K
1200 x 1100 x 2000 mm
Weight - UPS System (without power modules)
 
● DPH-300K
311 kg
● DPH-500K
317 kg
● DPH-600K
605 kg
Weight - 50 kW Power Module (optional)
36 kg
* The power module’s rating is adjustable to 50 kVA or 55.6 kVA via Modbus. DPH-500K can support 500 kVA / 450 kW with nine 55.6 kVA power modules.
** When input vTHD is less than 1%.

All specifications are subject to change without prior notice.

 