PRODUCT LIST

Precision Cooling - RowCool 70kW / 95kW, Chilled Water

Technical Specifications

Product available regions :
Because product specifications vary slightly from region to region, please download your local leaflet or visit your local website for detailed product information.
EMEA North America South America SEA India China Taiwan South Korea
     
 
RowCool 70kW
Model
HCH1CB0
 
HCH1CB0 with reheater/humidifier
Capacity
 
Maximum cooling capacity *1
70 kW
Sensible cooling capacity
69.3 kW
Power
 
Input power
3Φ4 W+G/50,60 Hz/ 380 V
Maximum input power
HCH1CB0: 3 kW
 
HCH1CB0 with reheater/humidifier: 14 kW
Maximum current
HCH1CB0: 5 AMP
 
HCH1CB0 with reheater/humidifier: 22 AMP
Fan
 
Air flow
11400 CMH (6700 CFM)
Type
EC Fan
Number of fans
3 n
Coil
 
Water flow
111.2 LPM
Reheater
(HCH1CB0 with reheater/humidifier)
Capacity
8.1 kW (27600 Btu/HR)
Current
12.3 Amp
Stages
3 n
Humidifier
(HCH1CB0 with reheater/humidifier)
Capacity
3 kg/h
Power consumption
2.25 kW
Current
3.5 Amp
Filter (disposable)
 
Filter classe
30-35 % MERV8
Tubing Dimensions
 
Inlet water
32 A mm (1 1/4 in) PT thread female
Outlet water
32 A mm (1 1/4 in) PT thread female
Drain pipe
20 A mm (3/4 in) PT thread male
Humidifier supply water
HCH1CB0 with reheater/humidifier:10 A mm (3/8 in)PT thread male
Connections of inlet/outlet water
Bottom / Top(optional)
Power Wiring
Both at top and bottom
Communication Interface
SNMP slot x1 (SNMP card is optional), RS232x1, RS485x1 (Modbus protocol), Input dry contact x2, Output dry contact x2, Temperature sensor x3, Remote temperature/humidity sensor x1
Accessories
SNMP card, Connection tube for top tubing, Humidifier accessory kit, reheater accessory kit, Remote temperature/humidity sensor, Drain Pump, Washable filter
Physical
 
Height (wo/w packaging)
2000 / 2220 mm
Width (wo/w packaging)
600 / 764 mm
Depth (wo/w packaging)
1090 / 1342 mm
Weight (Gross / Operating)
HCH1CB0: 368 / 414 kg
 
HCH1CB0 with reheater/humidifier: 375 / 421 kg
Please contact Delta or a local distributor for new specifications regarding the constant improvements Delta makes for various lines of products.
1. Testing standard of cooling capacity at 60Hz
Returned air 40.6°C (DB) / 21.6°C(WB)
Incoming chilled water temperature 7.2 °C
Temperature difference of inlet and outlet chilled water 8.8 °C

2. Reference for cooling capacity testing: ASHARE 127 and GB/T 19413-2003

3. Operation conditions: inlet water temperature 5~15°C, return air temperature 4~40°C DB, 30~85% non-condensing

4. Specifications are subject to change due to constant product updates

RowCool 95kW
Model
HCH1CD0
 
HCH1CD0 with Humidity Control
Power
Input power : 3N~, 380V, 50/60Hz
 
Power consumption : 4.8kW
Rating capacity *
Capacity : 95.9 kW
 
Sensible Capacity : 95.9 kW
Max capacity **
Capacity : 122.7 kW
 
Sensible Capacity : 122.7 kW
Capacity at high inlet water ***
Capacity : 81.2 kW
 
Sensible Capacity : 81.2 kW
Fan
Type : EC fan
 
Quantity : 3 n.
Valve
Air flow : 14050 m3/h
 
Type : 2way
 
Max flow : 150 LPM
 
Inlet water temp. range : 5~22°C
Reheater
Type : Electric heater
(HCH1CD0 with Humidity Control)
Capacity : 8.1 kW
Humidifier
Type : Electrode
(HCH1CD0 with Humidity Control)
Capacity : 3 kg/h
Filter
Type : MERV 1
Connection
Inlet pipe : 1 1/4” PT Female
 
Outlet pipe : 1 1/4” PT Female
 
Drain pipe : 3/4” ID
Dimension (W x D x H)
600 x 1090 x 2000 mm
Weight
HCH1CD0 : 415 kg
 
HCH1CD0 with Humidity Control : 422 kg
* Operation conditions: 40.6°C (DB), 21.6°C (WB), inlet water temperature 7°C, rated water flow
** Operation conditions: 48.9°C (DB), 23.9°C (WB), inlet water temperature 7°C, maximum water flow
*** Operation conditions: 40.6°C (DB), 21.6°C (WB), inlet water temperature 12°C, temperature difference 9°C
 