PRODUCT LIST

Power Distribution Unit

Technical Specifications

Product available regions :
Because product specifications vary slightly from region to region, please download your local leaflet or visit your local website for detailed product information.
EMEA North America South America SEA India China Taiwan South Korea
 
Model
PDU 80 / PDU 125
Capacity
[PDU 80]: 80kVA
 
[PDU 125]: 125 kVA
Input
 
Rated voltage
220/380 Vac, 3 phase 3 wire+ ground, or 3 phase 4 wire+ ground
Voltage tolerance range
±15%
Frequency
50 / 60 Hz ±5% (Automatic detection)
Output
 
Rated voltage
220/380 Vac, 3 phase 4 wire+ ground,
Total switching capacity
Based on actual product specifications
Switchboard type
Two groups of switchboards and 42 poles each
Shunt switch type
Hot-swap switch capacity: 15 / 20 / 30A,
 
Optional: 1/2/3 pole
Transformer
 
Input-Output Type
Δ-Y
Efficiency
97.5% (Full-load)
LCD Display
 
System
Temperature, ground current, System overheat alarm, V-Loss Alarm, Voltage Imbalance Alarm, Ground Fault Alarm
Blue light 4.9” graphic interface
 
Input
Phase voltage, line voltage, phase current, line current, load(%), iTHD, total kVA, total kW, total kWh, Over voltage/over current alarm, under-voltage/nder current alarm, Over line current alarm, iTHD abnormal alarm
Total output
Phase voltage, line voltage, phase current, line current, frequency, neutral current, load(%), kVA, kW, kWh, power factor, VTHD, iTHD, Over voltage/over current alarm, under-voltage/under current alarm, Over line current alarm, iTHD abnormal alarm, VTHD abnormal alarm, power factor abnormal alarm
Output shunt plate
phase current, kVA, kW, kWh, load (%), iTHD, power factor, line current, over current alarm, under current alarm, Over line current alarm, iTHD abnormal alarm, power factor abnormal alarm
Output shunt
Current, load (%), over current alarm, under current alarm
Temperature
Environment (instant and alarm), transformers (two stage-alarm)
Regulatory Compliance
 
Environment
CE
Electromagnetic interference
EN55022
Communication interface
RS232 x 1, dry contact x 6, SNMP slot x 2
Optional accessories
Lightning protector
Size (width, depth, height)
600 x 1090 x 2000mm standard 19” cabinet
Weight
Excluding transformer: 225kg, including H transformer: 80kVA: 525 kg, 125 kVA: 630 kg
These specifications are subject to change without notice. Please contact us or our distributors in your region for the latest specs.
 