Model
EMS1000 / EMS1100 / EMS1200
Input Voltage
EMS2000 Delta-BUS or SNMP Card: 12 Vdc (pin 1 & 4)
PDU SNMP card: 5 Vdc (Pin 2 & 4)
Purpose
● EMS1000
To collect data from connected devices (temperature & humidity)
● EMS1100
To control connected devices
● EMS1200
To collect data from and control connected devices
Input/Output Contacts
● EMS1000
4 dry/wet contact inputs
Connect to EnviroStation(EMS2000) or SNMP IPv6 card
● EMS1100
4 digital outputs
Connect to EnviroStation(EMS2000) or SNMP IPv6 card
● EMS1200
2 analog inputs, 1 analog output, 1 water-leakage detection (builtin buzzer)
Connect to EnviroStation (EMS2000)
Input
● EMS1000
Wet Contacts:5~24 Vdc, 1~8 mA
Dry Contacts: Open/Short Status
● EMS1100
N/A
● EMS1200
Voltage: 0~10 Vdc (12 bit)
Current: 0~20 mA (12 bit)
Output
● EMS1000
N/A
● EMS1100
Contact voltage/Contact current/Contact tolerance
60 Vdc / 1 A / 60 W, 30 Vac / 2.08 A / 62.5 VA
● EMS1200
Voltage: 0~10 Vdc (12 bit)
Current: 4~20 mA (12 bit)
Cascade number to EMS2000
● EMS1000
Up to 16 units
● EMS1100
Up to 4 units
● EMS1200
Up to 5 units
Dimensions (W x D x H)
Product
66 x 33 x 103 mm
Package
91 x 42 x 133 mm
Weight
● EMS1000
Net Weight: 120 g, Gross Weight: 140 g
● EMS1100 / EMS1200
Net Weight: 130 g, Gross Weight: 150 g
Environment - Temperature
Operation
0~60°C
Storage
● EMS1000
-20~60°C
● EMS1100 / EMS1200
0~60°C
Accuracy
● EMS1000
± 0.4°C & 0~60°C
● EMS1100 / EMS1200
N/A
Environment - Humidity
Operation
0~90% RH (no condensation)
Storage
0~100% RH (no condensation)
Accuracy
● EMS1000
± 3°C & 0~80°C
● EMS1100 / EMS1200
N/A
Environment - Altitude
● EMS1000 / EMS1100 / EMS1200
0~10,000 feet
Conformance
CE
EN55022 (CISPR 22) Class B
EN55024 (Level 3 @Air 8KV / contact 4KV)