PRODUCT LIST

DELTA UPS FAMILIES

UPS Amplon Family 1kVA or higher
Single-Phase UPS
Delta UPS Amplon Family
UPS Ultron Family 10kVA or higher
Three-Phase On-Line UPS
Delta UPS Ultron Family
UPS Modulon Family 20kVA or higher
Modular UPS
Delta UPS Modulon Family
UPS Agilon Family Under 1.5kVA or higher
Single-Phase UPS
Delta UPS Agilon Family

Ultron HPH Series UPS, Three Phase, 20/30/40/60/80/100/120 kW

Technical Specifications

Product available regions :
Because product specifications vary slightly from region to region, please download your local leaflet or visit your local website for detailed product information.
EMEA North America South America SEA India China Taiwan South Korea

(20-60kVA, 208/120V)

(20-40kVA)
 
Model
HPH-20K, HPH-30K, HPH-40K,
 
HPH-60K, HPH-80K, HPH-100K, HPH-120K
 
HPH-20K-BN/B, HPH-30K-BN/B, HPH-40K-BN/B
Power Rating
[20K]: 20 kVA/kW
 
[30K]: 30 kVA/kW
 
[40K]: 40 kVA/kW
 
[60K]: 60 kVA/kW
 
[80K]: 80 kVA/kW
 
[100K]: 100 kVA/kW
 
[120K]: 120 kVA/kW
Input
 
Nominal Voltage
380/220Vac, 400/230Vac, 415/240Vac (3 phase, 4-wire + G)
Voltage Range
[20-40K]: 300~477 Vac (full load), 228~300 Vac (70%~100% load)
 
[60-120K]: 332~477 Vac (full load), 228~332 Vac (63%~100% load)
Frequency
40~70Hz
Power Factor
> 0.99 (full load)
Current Harmonic Distortion
< 3%
Output
 
Voltage
380/220Vac, 400/230Vac, 415/240Vac (3 phase, 4-wire + G)
Voltage Regulation
± 1 %
Voltage Harmonic Distortion
[20-40K]: < 1.5% (linear load)
 
[60-120K]: <2% (linear load)
Overload Capability
≤105 %: continuous
 
106% ~ ≤125%: 10 minutes
 
126% ~ ≤150%: 1 minute
 
>150%: 1 second
Output Power Factor
1
Frequency
50/60Hz +/- 0.05Hz
Battery
 
Battery Voltage
240Vdc
Type
Support SMF/VRLA/Tubular/Ni-Cd
Quantity
[20-40K]: 32-50 pcs
 
[60-120K]: 32-46 pcs***
Charge Current (Max.)
[20K]: 5A
Built-in
[30/40K]: 9A
 
[60K]: 10A
 
[80K]: 15A
 
[100/120K]: 20A
Typical Backup Time**
[20K-BN/B]: 15 min
 
[30K-BN/B]: 10 min
 
[40K-BN/B]: 9.5 min
Communication Interfaces
SMART Slot x 1, MINI Slot x 1, Parallel Port x 2, RS232 Port x 1, REPO Port x 1, Charger Detection Port x 1, Input Dry Contact x 2, Output Dry Contact x 6, USB Port x 1*
Conformance
 
Safety
CE, RCM
UPS Classification According to IEC 62040-3
VFI-SS-111
Other Features
 
Parallel Redundancy
Up to 4 units
Emergency Power Off
Yes (local and remote)
Maintenance Bypass Switch
Yes
Efficiency
 
AC-AC
[20-40K]: Up to 96%
 
[60-120K]: > 96% (HPH 40-120K efficiency is tested by TÜV)
ECO Mode
Up to 99%
Environment
 
Operating Temperature
0 ~ 40˚C
Relative Humidity
5% ~ 95% (non-condensing)
Audible Noise
[20K]: < 55 dB
 
[30/40K]: < 60 dB
 
[60-120K]: < 65 dB
Physical
 
Dimensions (W x D x H)
[20-40K]: 380 x 800 x 800 mm
 
[60/80K]: 520 x 800 x 1175 mm
 
[100/120K]: 520 x 800 x 1760 mm
Weight
[20K]: 66.5 Kg
 
[30K]: 86.06 kg
 
[40K]: 86.5 Kg
 
[60K]: 186.5 kg
 
[80K]: 191 kg
 
[100/120K]: 312 kg
Physical (BN/B)
 
Dimensions (W x D x H)
[20-40K]: 490 x 830 x 1400 mm
Weight (with batt.)
[20K-B]: 365 kg
 
[30K/40K-B]: 385 kg
Weight (without batt.)
[20K-BN]: 131 kg
 
[30/40K-BN]: 162 kg
HPH-B: UPS integrated battery model has batteries inside
HPH-BN: UPS integrated battery model has no batteries inside

* Applied for models HPH-60/80/100/120K
** At 70% load with internal battery strings.
*** UPS needs de-rating for battery quantity 32-36 pcs. Please contact authorized Delta personnel.

All specifications are subject to change without prior notice.

 

TUV Rheinland   RCM- compliance
Delta Ultron HPH 40~120kVA
Efficiency is tested by TÜV
Applied for models HPH-20/30/40K

 
Request A Quote
First Name *
Last Name *
Company *
Job Title *
Work Email *
Work Phone *
State / Province
Country *
Products you are interested in *
Message *
Subscribe Newsletter *
 

top