Model
RT-1K / RT-2K / RT-3K
Power Rating:
● RT-1K
1 kVA / 0.9 kW
● RT-2K
2 kVA / 1.8 kW
● RT-3K
3 kVA / 2.7 kW
Input
Nominal Voltage
200*/208*/220/230/240 Vac
Voltage Range
175~280 Vac (full load)
120~175 Vac (70~100% load)
Frequency
40~70 Hz
Power Factor
> 0.99 (full load)
Current Harmonic Distortion
< 5%
Output
Power Factor
0.9
Voltage
200*/208*/220/230/240 Vac
Voltage Regulation
± 1% (linear load)
Frequency
50/60 Hz ± 0.05 Hz
Voltage Harmonic Distortion
< 2% (linear load)
Overload Capability
< 105%: Continuous
105~125%: 1 minute
125~150%: 15 seconds
Receptacle:
● RT-1K
IEC C13 x 6
● RT-2K/3K
IEC C13 x 6, IEC C19 x 1
Efficiency
AC-AC:
● RT-1K
90%
● RT-2K/3K
Up to 94%
ECO Mode:
● RT-1K
96%
● RT-2K/3K
Up to 97%
Battery
Battery Voltage:
● RT-1K
24 Vdc
● RT-2K
48 Vdc
● RT-3K
72 Vdc
Typical Backup Time**:
● RT-1K
6.5 minutes
● RT-2K/3K
7 minutes
Charge Current:
● RT-1K
1.5 A
● RT-2K/3K
2 A
Recharge Time
3 hours to 90%
Audible Noise:
● RT-1K
< 40 dBA
● RT-2K
< 43 dBA
● RT-3K
< 46 dBA
Display
LCD display and LED indicators
Interfaces
SMART Slot x 1, RS-232 Port x 1, USB Port x 1, REPO x 1
Conformance
CE, TISI, RCM, EAC
Dimensions (W x D x H)
UPS:
● RT-1K
440 x 335 x 89 mm
● RT-2K
440 x 432 x 89 mm
● RT-3K
440 x 610 x 89 mm
External Battery Pack:
● RT-1K
440 x 335 x 89 mm
● RT-2K
440 x 432 x 89 mm
● RT-3K
440 x 610 x 89 mm
Weight
UPS:
● RT-1K
12 kg
● RT-2K
18 kg
● RT-3K
28 kg
External Battery Pack:
● RT-1K
15 kg
● RT-2K
27 kg
● RT-3K
44 kg
Environment
Operating Temperature
0~50°C***
Relative Humidity
5~95% (non-condensing)
* When the UPS is de-rated to 90% of its capacity.
** When the total load reaches 75%.
*** 40~50°C with 80% de-rating.
** When the total load reaches 75%.
*** 40~50°C with 80% de-rating.