• Delta datacenter infrastructure total solutions
  • Modular UPS - DPH Series 20 – 80/120 kVA

    Technical Specifications

    Product available regions:
    .
    North America South America
     

      

    Model
    DPH-80K / DPH-120K
    Power Rating
     
    ● DPH-80K
    20, 40, 60, 80 kVA/kW
     
    20 kW Power Module: Up to 4 units
    ● DPH-120K
    20, 40, 60, 80, 100, 120 kVA/kW
     
    20 kW Power Module: Up to 6 units
    Input
     
    Nominal Voltage
    220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)
    Voltage Range
    305~478 Vac (full load), 228~478 Vac (70% load)
    Current Harmonic Distortion
    ≤ 2%*
    Power Factor
    > 0.99
    Frequency Range
    40~70 Hz
    Output
     
    Voltage
    220/380 Vac, 230/400 Vac, 240/415 Vac (3-phase, 4-wire + G)
    Voltage Harmonic Distortion
    ≤ 1% (linear load)
     
    ≤ 4% (non-linear load)
    Voltage Regulation
    ±1% (static)
    Frequency
    50/60 Hz
    Overload Capability
    ≤ 125%: 10 minutes
     
    ≤ 150%: 1 minute
     
    > 150%: 1 second
    Display
    10” color touch screen
    Interface
     
    Standard
    External battery temperature detection x 4, External switch/breaker status dry contact x 4, Output dry contact x 6, Input dry contact x 4, Parallel port x 2, USB Port (Type A x 2, Type B x 1), RS232 Port x 1, Modbus Port x 1, BMS (RJ45) x 1, Ethernet x 1, SNMP Slot x 1, REPO Port x 1
    Conformance
     
    Safety
    CE
    Efficiency
     
    AC-AC
    > 96% (Peak efficiency)
    ECO Mode
    99%
    Battery
     
    Nominal Voltage
    ±240 Vdc (default, ±180~±276 Vdc configurable)
    Charge Voltage
    ±272 Vdc (adjustable from 204 to 312 V)
    Protection of Battery Deep Discharge
    Yes
    Environment
     
    Operating Temperature
    0~40℃
    Relative Humidity
    95% (non-condensing)
    Audible Noise (at one meter)
    < 65 dB
    IP Protection
    IP20
    Others
     
    Parallel Redundancy and Expansion
    Module and system redundancy, Maximum 8 units
    Battery Start
    Yes
    Physical
     
    Dimensions (W x D x H)
    600 x 850 x 1445 mm
    Weight - UPS System (without power modules)
     
    ● DPH-80K
    150 kg
    ● DPH-120K
    162 kg
    Weight - 20 kW Power Module (optional)
    18 kg
    * When input voltage total harmonic distortion input is less than 1%

    All specifications are subject to change without prior notice. 

     
    Request A Quote
    First Name *
    Last Name *
    Company *
    Job Title *
    Work Email *
    Work Phone *
    State / Province
    Country *
    Products you are interested in *
    Message *
    Subscribe Newsletter *
     

    top