PRODUCT LIST

EnviroProbe

Technical Specifications

Model
EMS1000 / EMS1100 / EMS1200
Input Voltage
EMS2000 Delta-BUS or SNMP Card: 12 Vdc (pin 1 & 4)
 
PDU SNMP card: 5 Vdc (Pin 2 & 4)
Purpose
 
● EMS1000
To collect data from connected devices (temperature & humidity)
● EMS1100
To control connected devices
● EMS1200
To collect data from and control connected devices
Input/Output Contacts
 
● EMS1000
4 dry/wet contact inputs
 
Connect to EnviroStation(EMS2000) or SNMP IPv6 card
● EMS1100
4 digital outputs
 
Connect to EnviroStation(EMS2000) or SNMP IPv6 card
● EMS1200
2 analog inputs, 1 analog output, 1 water-leakage detection (builtin buzzer)
 
Connect to EnviroStation (EMS2000)
Input
 
● EMS1000
Wet Contacts:5~24 Vdc, 1~8 mA
 
Dry Contacts: Open/Short Status
● EMS1100
N/A
● EMS1200
Voltage: 0~10 Vdc (12 bit)
 
Current: 0~20 mA (12 bit)
Output
 
EMS1000
N/A
EMS1100
Contact voltage/Contact current/Contact tolerance
 
60 Vdc / 1 A / 60 W, 30 Vac / 2.08 A / 62.5 VA
EMS1200
Voltage: 0~10 Vdc (12 bit)
 
Current: 4~20 mA (12 bit)
Cascade number to EMS2000
 
● EMS1000
Up to 16 units
● EMS1100
Up to 4 units
● EMS1200
Up to 5 units
Dimensions (W x D x H)
 
Product
66 x 33 x 103 mm
Package
91 x 42 x 133 mm
Weight
 
● EMS1000
Net Weight: 120 g
 
Gross Weight: 140 g
● EMS1100/1200
Net Weight: 130 g
 
Gross Weight: 150 g
Environment - Temperature
 
Operation
0~60°C
Storage
 
● EMS1000
-20~60°C
● EMS1100/1200
0~60°C
Accuracy
 
● EMS1000
± 0.4°C & 0~60°C
● EMS1100/1200
N/A
Environment - Humidity
 
Operation
0~90% RH (no condensation)
Storage
0~100% RH (no condensation)
Accuracy
 
● EMS1000
± 3°C & 0~80°C
● EMS1100/1200
N/A
Environment - Altitude
0~10,000 feet
Conformance
CE
 
EN55022 (CISPR 22) Class B
 
EN55024 (Level 3 @Air 8 KV/contact 4 KV)
These specifications are subject to change without notice. Please contact us or our distributors in your region for the latest specs.
 