• Modulon DPH 300/500/600 kVA
  • DPH Series UPS, Three Phase, 50- 300/500/600 kVA

    Technical Specifications

    Model
    DPH-300K / DPH-500K / DPH-600K
    Power Rating
     
    ● DPH-300K
    50-300 kVA/kW
     
    50 kW Power Module: Up to 6 units
    ● DPH-500K
    50-500 * kVA / 50-450 kW
     
    50 kW Power Module: Up to 9 units
    ● DPH-600K
    50-600 kVA/kW
     
    50 kW Power Module: Up to 12 units
    Input
     
    Nominal Voltage
    220/380 V, 230/400 V, 240/415 V (3-phase, 4-wire + G)
    Voltage Range
    305-477 Vac (full load), 229-305 Vac (70~100% load)
    Current Harmonic Distortion
    < 3% **
    Power Factor
    > 0.99
    Frequency Range
    40~70 Hz
    Output
     
    Voltage
    220/380 V, 230/400 V, 240/415 V (3-phase, 4-wire + G)
    Voltage Harmonic Distortion
    ≤ 0.5% (linear load)
    Voltage Regulation
    ± 1% (static)
    Frequency
    50/60 ± 0.05 Hz
    Overload Capability
    ≤ 125%: 10 minutes
     
    ≤ 150%: 1 minute
     
    > 150%: 1 second
    Display
    10” color touch screen
    Interface
     
    Standard
    RS232 x 1, Parallel port x 4, USB type A x 2, USB type B x 1, MODBUS x 1, Smart slot x 1, REPO x 1, EPO x 1, Input dry contact x 4, Output dry contact x 6, External battery temperature detection x 4, External switch/breaker status dry contact x 4, BMS (RJ45) x 1, Ethernet x 1
    Optional
    Relay I/O card, Battery cabinet temperature sensor cable
    Conformance
     
    Safety
    CE
    Efficiency
     
    AC-AC Mode
    Up to 96.5%
    ECO Mode
    99%
    Battery
     
    Nominal Voltage
    ±240 Vdc (default, ±180 Vdc to ±276 Vdc configurable)
    Charge Voltage
    ±272 V (adjustable from ±204 V to ±312 V)
    Protection of Battery Deep Discharge
    Yes
    Environment
     
    Operating Temperature
    0~40℃
    Relative Humidity
    0~90% (non-condensing)
    Audible Noise (at one meter)
     
    ● DPH-300K
    < 75 dB
    ● DPH-500K
    < 80 dB
    ● DPH-600K
    < 85 dB
    IP Protection
    IP20
    Others
     
    Parallel Redundancy and Expansion
    Module and system redundancy, Maximum 8 units
    Emergency Power Off
    Remote (default) and local (optional)
    Battery Start
    Yes
    Physical
     
    Dimensions (W x D x H)
     
    ● DPH-300K
    600 x 1100 x 2000 mm
    ● DPH-500K
    600 x 1100 x 2000 mm
    ● DPH-600K
    1200 x 1100 x 2000 mm
    Weight - UPS System (without power modules)
     
    ● DPH-300K
    311 kg
    ● DPH-500K
    317 kg
    ● DPH-600K
    605 kg
    Weight - 50 kW Power Module (optional)
    36 kg
    * The power module’s rating is adjustable to 50kVA or 55.6 kVA via Modbus. DPH-500K can support 500 kVA / 450 kW with nine 55.6 kVA power modules.
    ** When input vTHD is less than 1%.

    All specifications are subject to change without prior notice.