• Delta UPS Modulon family
  • DPH Series, Three Phase, 20-80/ 50-200 kVA

    Technical Specifications

    Model
    DPH-80K-FR / DPH-200K-FR
    Power Rating
     
    ● DPH-80K-FR
    20, 40, 60, 80 kVA/ kW
     
    Frame Size: 80 kW
    ● DPH-200K-FR
    50, 100, 150, 200 kVA/ kW
     
    Frame Size: 200 kW
    Parallel Configuration
    Up to 8 units
    Input
     
    Nominal Voltage
    380/ 400/ 415 Vac, 3P4W+PE
    Voltage Range
    176~276/ 305~477 Vac (Full Load)
     
    132~176/ 229~305 Vac (De-rated 70 % Load)
    Frequency
    40~70 Hz
    Total Harmonic Distortion (THDi)
    < 3 %
    Power Factor
    > 0.99 (full load)
    Output
     
    Nominal Voltage
    380/ 400/ 415 Vac, 3P4W+PE
    Voltage Regulation
    ±1 % (static)
    Frequency
    50/60 ± 0.05 Hz
    Total Harmonic Distortion (THDv)
    ≤ 2 % (Linear Load), ≤ 5 % (Non-linear Load)
    Power Factor
    1.0
    Overload Capability
    ≤ 125 %: 10 minutes
     
    ≤ 150 %: 1 minute
     
    > 150 %: 1 sec
    Current Crest Ratio
    3:1
    Efficiency
     
    Online Mode
    Up to 96.5 %
    ECO Mode
    Up to 99 %
    Battery
     
    Battery Type
    VRLA/ Vented lead-acid/ Lithium-ion battery
    Nominal Voltage
    ±240 Vdc
    Quantity
    40 pcs
    Charge Current
     
    ● DPH-80K-FR
    32 A (Max.)
    ● DPH-200K-FR
    75 A (Max.)
    Communication Interface
     
    Display
    10″ Color Touch Screen
    Port
    RS-485, CAN bus (to communicate with UPS system), EMS(RJ45), BMS(RS-232/RS-485), MODBUS
    Physical
     
    Dimensions (W x D x H)
    600 x 1109 x 2000 mm
    Net Weight
     
    - UPS System
     
    ● DPH-80K-FR
    269 kg
    ● DPH-200K-FR
    275 kg
    - Per Power Module
     
    ● DPH-80K-FR
    18 kg
    ● DPH-200K-FR
    36.9 kg
    - Per Battery Module
     
    ● DPH-80K-FR
    32.6 kg
    Environment
     
    Operating Temperature
    0 to 40 °C
    Humidity
    0~95 % (non-condensing)
    Audible Noise
     
    ● DPH-80K-FR
    < 65 dBA
    ● DPH-2000K-FR
    < 75 dBA
    Altitude
    0~1,000 m
    Storage Temperature
    -20 to +70 °C
    Ingress Protection
    IP20
    Conformance
     
    Safety
    CE, BSMI, RCM
    EMC
    IEC 62040-2
    Performance
    IEC 62040-3
    Sustainability
    RoHS, REACH
    Features
     
    Burn-in Test without Load Bank
    Standard
    Cold Start Function
    Standard
    Frequency Conversion
    Standard
    Failure Prediction
    Standard
    Software Integration with Delta Lithium Battery BMS
    Standard
    All specifications are subject to change without prior notice.
    Request A Quote
    First Name *
    Last Name *
    Company *
    Job Title *
    Work Email *
    Phone *
    State / City
    Country *
    Products you are interested in *
    Message *
    Subscribe Newsletter *
     