PRODUCT LIST
DELTA UPS FAMILIES
RT Series UPS, Single Phase, 5/6/8/10 kVA, 208V
Technical Specifications
Model
RT-5K / RT-6K / RT-8K / RT-10K
Power Rating
220/230/240V
[5K]: 5kVA / 5kW
[6K]: 6kVA / 6kW
[8K]: 8kVA / 8kW
[10K]: 10kVA / 10kW
2001)/208V
[5K]: 5kVA / 4.5kW
[6K]: 6kVA / 6kW
[8K]: 8kVA / 8kW
[10K]: 10kVA / 10kW
Input
Voltage Range
100 ~ 280V, 100 ~ 175V with linear de-rating 50 ~ 100%
Frequency
40 ~ 70 Hz
Power Factor
> 0.99 (full load)
iTHD
< 3%
Input Connection
Standard Runtime Model
[5K]: NEMA L6-30P
[6K/8K/10K]: Terminal
Extended Runtime Model
Terminal
Output
Power Factor
Unity 2)
Voltage
2001)/208/220/230/240 Vac
Frequency
50/60 Hz
Voltage Harmonic Distortion
≤ 2% (linear load)
Overload Capability
≤ 105%: Continuous
105 ~ 125%: 2mins
125 ~ 150%: 30secs
150%: 500ms
Receptacle
Standard Runtime Model
[5K]: L6-20 x 2, L6-30 x 1, Load bank: L6-30 x 1
[6K]: L6-20 x 2, L6-30 x 1, Terminal x 1, Load bank: L6-30 x 1
[8K]: L6-20 x 2, L6-30 x 2, Terminal x 1, Load bank: L6-30 x 1
[10K]: L6-20 x 2, L6-30 x 2, Terminal x 1, Load bank: L6-30 x 1
Extended Runtime Model
Terminal x 1, Load bank: Terminal x 1
Efficiency
AC-AC
Up to 95.5%
ECO Mode
Up to 98.5%
Battery Voltage
Standard Runtime Model
[5K]: 192 Vdc
[6K]: 192 Vdc
[8K]: 240 Vdc
[10K]: 240 Vdc
Extended Runtime Model
144 Vdc 3), 192 ~ 240 Vdc
Charger Current
Standard Runtime Model
[5K/6K]: 1A (default)
[8K/10K]: 1.5A (default)
Extended Runtime Model
Up to 8A
Discharge Time (Standard Runtime Model)
Full load
[5K]: 5 min.
[6K]: 3 min.
[8K]: 5 min.
[10K]: 3.5 min.
75% load
[5K]: 7.5 min.
[6K]: 5.5 min.
[8K]: 9 min.
[10K]: 6 min.
Recharge Time
Standard Runtime Model: 3 hrs to 90%
Audible Noise
[5K/6K]: 48 dB
[8K/10K]: 50 dB
Display
Graphical and multi-lingual LCD
Communication
Interfaces
Mini Slot x 1, RS-232 Port x 1, RS-485 Port x 1, USB Port x 1, REPO/ROO, Dry Contact x 4
Dimensions (W x D x H)
Standard Runtime Model
[5K/6K]: 17.3 x 26.2 x 6.9 inch (440 x 665 x 176 mm)
[8K/10K]: 17.3 x 29.5 x 8.6 inch (440 x 750 x 218 mm)
Extended Runtime Model
[5K/6K]: 17.3 x 16.9 x 3.3 inch (440 x 430 x 88 mm)
[8K/10K]: 17.3 x 22.2 x 3.3 inch (440 x 565 x 88 mm)
VRLA Battery Pack
[5K/6K]: 17.3 x 22.2 x 3.5 inch (440 x 565 x 88 mm)
[8K/10K]: 17.3 x 25.6 x 5.1 inch (440 x 650 x 130 mm)
Li-lion Battery Pack *
17.3 x 25.4 x 3.5 inch (440 x 646 x 88 mm)
* Only applicable to Extend Runtime Model
Weight
Standard Model
[5K]: 121.2 lbs (55 kg)
[6K]: 121.2 lbs (55 kg)
[8K]: 189.6 lbs (86 kg)
[10K]: 189.6 lbs (86 kg)
Environment
Operating Temperature
32 ~ 131°F (0 ~ 50°C) 4)
Relative Humidity
5 ~ 95% (non-condensing)
1) Under 200V, de-rating to 90% load
2) Under 200/208V, 5kVA standard runtime model O/P PF = 0.9
3) De-rating to 80% load
4) Full load @ 32 ~ 104°F (0 ~ 40°C), de-rating to 75% @ 104 ~ 131°F (40 ~ 55°C)
All specifications are subject to change without prior notice.
2) Under 200/208V, 5kVA standard runtime model O/P PF = 0.9
3) De-rating to 80% load
4) Full load @ 32 ~ 104°F (0 ~ 40°C), de-rating to 75% @ 104 ~ 131°F (40 ~ 55°C)
All specifications are subject to change without prior notice.
Request A Quote |