Listado de Productos
DATACENTER CATEGORIES
Power Distribution Unit
Technical Specifications
Model                
                
PDC 80 / PDC 125                 
                
            
Capacity                
                
[PDC 80]: 80kVA                 
                
            
[PDC 125]: 125 kVA                 
                
            
Input                 
                
Rated voltage                
                
220/380 Vac, 3 phase 3 wire+ ground, or 3 phase 4 wire+ ground                 
                
            
Voltage tolerance range                
                
±15%                 
                
            
Frequency                
                
50 / 60 Hz ±5% (Automatic detection)                 
                
            
Output                 
                
Rated voltage                
                
220/380 Vac, 3 phase 4 wire+ ground,                 
                
            
Total switching capacity                
                
Based on actual product specifications                 
                
            
Switchboard type                
                
Two groups of switchboards and 42 poles each                 
                
            
Shunt switch type                
                
Hot-swap switch capacity: 15 / 20 / 30A,                 
                
            
Optional: 1/2/3 pole                 
                
            
Transformer                 
                
Input-Output Type                
                
Δ-Y                 
                
            
Efficiency                
                
97.5% (Full-load)                 
                
            
LCD Display                 
                
System                
                
Temperature, ground current, System overheat alarm, V-Loss Alarm, Voltage Imbalance Alarm, Ground Fault Alarm                 
                
            
Blue light 4.9” graphic interface.                 
                
Input                
                
Phase voltage, line voltage, phase current, line current, load(%), iTHD, total kVA, total kW, total kWh, Over voltage/over current alarm, under-voltage/nder current alarm, Over line current alarm, iTHD abnormal alarm                 
                
            
Total output                
                
Phase voltage, line voltage, phase current, line current, frequency, neutral current, load(%), kVA, kW, kWh, power factor, VTHD, iTHD, Over voltage/over current alarm, under-voltage/under current alarm, Over line current alarm, iTHD abnormal alarm, VTHD abnormal alarm, power factor abnormal alarm                 
                
            
Output shunt plate                
                
phase current, kVA, kW, kWh, load (%), iTHD, power factor, line current, over current alarm, under current alarm, Over line current alarm, iTHD abnormal alarm, power factor abnormal alarm                 
                
            
Output shunt                
                
Current, load (%), over current alarm, under current alarm                 
                
            
Temperature                
                
Environment (instant and alarm), transformers (two stage-alarm)                 
                
            
Regulatory Compliance                 
                
Environment                
                
CE                 
                
            
Electromagnetic interference                
                
EN55022                 
                
            
Communication interface                
                
RS232 x 1, dry contact x 6, SNMP slot x 2                 
                
            
Optional accessories                
                
Lightning protector                 
                
            
Size (width, depth, height)                
                
600 x 1090 x 2000mm standard 19” cabinet                 
                
            
Weight                
                
Excluding transformer: 225kg, including H transformer: 80kVA: 525 kg, 125 kVA: 630 kg                
                
            
    
    
    