Busway System - BL Series

Technical Specifications

Busway
 
Rating
400/ 600/ 800/ 1000/ 1250/ 1500/ 1600/ 2000/ 2500/
 
3200/ 4000/ 5000/ 6400 A
Rating - UL
250/ 400/ 600/ 800/ 1000/ 1250/ 1500/ 1600/ 2000/
 
2500/ 3200/ 4000/ 5000 A
Rated Voltage
1000 V
Frequency
50/60 Hz
Conductor
Copper purity: 99.9% conductivity: 99.9% IACS
 
Aluminum purity: 98.0% conductivity: 56.0% IACS
Conductor Plating
Tin plating
Insulation Material
Epoxy Cast resin
Insulation Class
F class 155°C
Fire Resistance
IEC60331 750°C 3 hrs, IEC60332
 
CNS12514 840°C 30 mins (Special made-C)
Ingress Protection rating
IP68
Earthquake Test
0.8 g (magnitude > 7)
Explosive-symbol
ExmII
Mechanical Impact
IK10
Color
RAL7043
Plug-in Unit
 
Type
Plug-in type / Bolt-on type
Pole
1P/2P/3P/4P
Max. Rating
Plug-in type 630 A
 
Bolt-on type 2000 A
MCCB Brands
Mitsubishi, Fuji, GE, Schneider (MG), or Customer specified
Protection Rating
IP42 / IP55 (Optional)
Panel Coating
Powder coated paint
Coating Thickness
Indoor 40μm / outdoor 50μm
Color
RAL7047 / RAL7043
General
 
Standards
IEC60439-2,IEC61439,IEC60529,IEC60331,IEC60332
 
JIS C8364,JIS A1304,JIS H3140
 
GB7251.1,GB7251.2, ANSI / UL857,NEMA BU-1
Ambient Temperature
-20°C/+50°C avg.35°C
Altitude
≤ 2,000 m
 

Product available regions:

North America Latin America
250-5000 A (UL) 400-6400 A

  

 